Product information "Circuit-breaker EB2 250/4H 250A, Icu 65kA / Ics 36kA"

Ics: 36kA
Icu: 65kA
Number of poles: 4
Rated current: 250A
Rated voltage: 690V
Setting value Magnetic: 6-10 x In
Thermal setting value: 0.63-1 x In
Skip product gallery

Accessories for circuit-breaker EB2 250/4H 250A, Icu 65kA / Ics 36kA

Terminal cover PRS2 160-250/4 front, for EB2 160-250
Terminal cover PRS2 160-250/4 front, for EB2 160-250

Mounting from above only.

Regular price: CHF 50.2163
Terminal cover PRS2 160-250/4 Cable connections, for EB2 160-250
Terminal cover PRS2 160-250/4 Cable connections, for EB2 160-250

Two-part design for top and bottom.

Regular price: CHF 21.2552
Undervoltage release NA2, 125-630AF, 24VDC, for EB2 125-630
Undervoltage release NA2, 125-630AF, 24VDC, for EB2 125-630

Cannot be installed together with shunt outlet

Regular price: CHF 99.9245
Auxiliary switch, PS2 125-1600AF, 1W, for EB2 125 - 1600
Auxiliary switch, PS2 125-1600AF, 1W, for EB2 125 - 1600

For all EB2 sizes. I = 3A with resistive load with 24VCD/240VAC.

Regular price: CHF 28.9612
Signal switch SS2 125-1600AF, 1W, for EB2 125 - 1600
Signal switch SS2 125-1600AF, 1W, for EB2 125 - 1600

For all EB2 sizes. I = 3A with resistive load with 24VCD/240VAC.

Regular price: CHF 28.7071
Electric motor drive MO2 250, 230-240V AC, for EB2 160-250
Electric motor drive MO2 250, 230-240V AC, for EB2 160-250

Voltage range 85%-110%. Load current on actuation 3.5-7A depending on the applied voltage. As the motorised drive is designed for a short-term load, it must cool down for at least 15 minutes after 10 consecutive on/off cycles to ensure safe operation.

Regular price: CHF 891.9374
Electric motor drive MO2 250, 230-240VAC, with reset, for EB2 160-250
Electric motor drive MO2 250, 230-240VAC, with reset, for EB2 160-250

Voltage range 85%-110%. Load current during operation depending on the applied voltage at 3.5-7A. As the motorised drive is designed for a short-term load, it must cool down for at least 15 minutes after 10 consecutive on/off cycles to ensure safe operation.

Regular price: CHF 891.9374
Skip product gallery

Customers also viewed

QS NH switch-disconnector strip with fuses size 00, 185mm, AU-M8, high version
QS NH switch-disconnector strip with fuses size 00, 185mm, AU-M8, high version

QUADRON®185Power Speed CrossLink contacting (integrated busbar terminals) When the cover is open, all accessible parts are de-energised Operator-independent switching (switching without protective equipment) Lockable cover with double-bit lock Mixed installation with all 185 Power components Can be sealed when switched on and off Can be locked with up to 3 shackle locks when switched off The use of disconnecting blades is not approved. The rated values specified in this product description apply exclusively to the use of fuses.