Product information "Janitza power quality analyser (class S according to IEC 61000-4-30) UMG 605-PRO - 24V"
The power quality analyser, in accordance with EN 50160, is particularly suitable for DIN rail mounting. It is used to monitor the power quality in accordance with common standards, e.g. EN 6100024. The UMG 605-PRO is suitable for detecting short and long-term flicker as well as for Profibus DP and Profibus DP V0. The UMG has two digital inputs and outputs and an additional temperature measurement input.
4th current transformer input: | Yes |
---|---|
Accuracy A: | 0.25% |
Accuracy V: | 0.2% |
Active energy class: | 0.5S (.../5 A) |
Analogue output: | None |
Asymmetry: | Yes |
Clock: | Yes |
Current measuring channels: | 4 |
Digital / pulse output: | 2 |
Digital inputs: | 2 |
Distortion factor THD-U / THD-I in %: | Yes |
Execution of the interface: | Modbus RTU RS232, Modbus RTU RS485, Profibus DP VO , TCP/IP (Ethernet / network) |
Fault recorder function: | Yes |
Harmonics V/A: | 1.-63. |
Integrated logic: | Jasic (7 prg.) |
Memory min / max values: | Yes |
Memory size: | 128 MB |
Quadrants: | 4 |
Residual current inputs: | None |
Sampling frequency 50/60 Hz: | 20 kHz |
Short-term interruptions: | Yes |
Short / long-term flicker: | Yes |
Supply voltage: | 24 - 90V AC & 24 - 90V DC |
Temperature input: | 1 |
Transients: | > 50 µs |
Web server / e-mail: | Yes |